Thread: lyman 230v 850 watt furnace

  1. #1
    Boolit Mold
    Join Date
    Jun 2012
    Posts
    24

    lyman 230v 850 watt furnace

    Hello all , my kids got me a lyman big dipper furnace this past Christmas. I finally opened it up,only to find a goofy looking plug and its marked 230v 850 watts. What do I do now ?, returning isn't a option. I see plug adapters ? , but if it will run on 110 I'll just swap plugs.
    Thanks all

  2. #2
    Boolit Buddy
    Join Date
    Jul 2011
    Location
    Ogilvie Mn
    Posts
    483
    At approx 1/2 output the heating element will run on 110 will that be enough to do the job not sure seems kind low

  3. #3
    Boolit Buddy Daddyfixit's Avatar
    Join Date
    Nov 2009
    Location
    Washington
    Posts
    394
    I don't know what room your drier is in but it runs on 220. Goodwill stores always have used drier pig tail harnesses cheep or if your breaker box is in the garage wire up a plug there.

  4. #4
    Boolit Mold
    Join Date
    Jun 2012
    Posts
    24
    thanks all

  5. #5
    Boolit Master


    Join Date
    Jun 2009
    Location
    southwest Louisiana
    Posts
    983
    Quote Originally Posted by hound-1 View Post
    Hello all , my kids got me a lyman big dipper furnace this past Christmas. I finally opened it up,only to find a goofy looking plug and its marked 230v 850 watts. What do I do now ?, returning isn't a option. I see plug adapters ? , but if it will run on 110 I'll just swap plugs.
    Thanks all

    Nope. If you cut the voltage in half, you get a QUARTER of the power, so your 850-watt pot is going to put out 212 watts. You can warm your coffee on it, but that's about it.

    We use this trick all the time in the electrical power business. A thousand watt 240-volt heater is run at 120 volts. Gives 250 watts. Lasts forever.

    IF you're of a mind to look at the math, heat is I-squared times R. If you cut the voltage in half, you get half the current. 1/2 squared is 1/4. That's how much heat you get. A quarter.

    dale in Louisiana

  6. #6
    Boolit Master

    monadnock#5's Avatar
    Join Date
    Mar 2006
    Location
    New Hampshire
    Posts
    1,270
    +1 on tapping the dryer circuit. Don't run them both at the at the same time though. Even if it doesn't overload the breaker, you'll suck amps so hard it'll burn the bearings out of the meter.
    You have enemies? Good. That means you've stood up for something, sometime in your life.
    Winston Churchill

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •  
Abbreviations used in Reloading

BP Bronze Point IMR Improved Military Rifle PTD Pointed
BR Bench Rest M Magnum RN Round Nose
BT Boat Tail PL Power-Lokt SP Soft Point
C Compressed Charge PR Primer SPCL Soft Point "Core-Lokt"
HP Hollow Point PSPCL Pointed Soft Point "Core Lokt" C.O.L. Cartridge Overall Length
PSP Pointed Soft Point Spz Spitzer Point SBT Spitzer Boat Tail
LRN Lead Round Nose LWC Lead Wad Cutter LSWC Lead Semi Wad Cutter
GC Gas Check